Term
Substations
Describe the 345KV breakers. |
|
Definition
-All but 8N11 hydraulic operated w/ spring assist. -8N11 is air open/spring shut. -Low oil pressure <76#. -Low-low <72# (prevents trip/close). -8N11 <198# prevents open/close. -All have cycling heaters. |
|
|
Term
Substations.
Describe the 230Kv breakers. |
|
Definition
-OCBs. -Hydraulic close/spring open. -<1600# prevents closure. -Can still trip. |
|
|
Term
Substations
Describe the 3N4 to 3N5 interlock. |
|
Definition
-Supply to 2R transformer. -3N4 cannot be closed if 3N5 is closed. |
|
|
Term
Substations
Describe what happens if 3N4 opens. |
|
Definition
-Both recirc pumps trip. -Both circ water pumps trip. -Loss of either 11/12 bus. |
|
|
Term
Substations Describe the cooling tower substation. |
|
Definition
-Buss' 17 & 18 (13.8KV). -Has load centers 5 & 6 (4KV). -Powered from 1ARS and through 6 transformer. |
|
|
Term
Substations
Describe the breaker and a half scheme. |
|
Definition
-3 breakers share circuit. -Any 1 can be open and still maintain both circuits in service. |
|
|
Term
Substations
Describe breaker auto reclosure modes. |
|
Definition
-High speed or instantaneious. -Synchronous mode (3-6 sec delay). -Delayed reclosure (about 15 sec delay). |
|
|
Term
Substations
Describe auto-sectionalizing. |
|
Definition
-Isolate faulted equipment once circuit breakers have tripped. -Circuit breaker opens to denenergize faulted equipment. -Motor operated disconnect opens to isolate equipment. -Circuit breakers re-close once fault is isolated. |
|
|
Term
Substations
Describe breaker failure relay. |
|
Definition
-Sensed by detecting current flow after receiving breaker trip signal and breaker did not open. -If current is sensed after 12 cycles after breaker trip, breaker lockout is actuated. -All surrounding breakers to trip and all surrounding busses to lockout. |
|
|