DC Power Distribution

 

Purpose

Definition
To supply 250/125/28 VDC to Vital systems during  normal, transient, and accident conditions
Term

DC Power

Design Basis

Definition

250 VDC supplies highly reliable power to the Main Feed Pump and Main Turbine Generator emergency auxiliaries

125 VDC provide reliable control power to all plant auxiliaries. CW has its own seperate 125 VDC battery supply and chargers.

28 VDC supplies reliable control power to all plant auxiliaries.

NO initiation or control is needed to supply DC from the batteries to the bus.

All battery chargers carry all loads under normal power.

All Batteries are sized for 2 hours of operation during LOPA and chargers regain loads when EDGs come online.

Term
250 VDC Batteries...
Definition

1 bank per unit

120 cells at 2.2 v per cell

2A1 and 2A2 Primary and Backup Battery chargers.

Located on 100' in the 250 VDC battery room adjacent to the 125/28VDC battery room adjacent to the relay room.

 

FEED: #1 and #2 SGFP Emergency Oil Pump

Main Turbine Emergency Oil Pump

U1 and U2 Emergency Seal Oil Pumps

Term

Two modes of operation for all battery chargers are?

 

State each modes purpose....

Definition

1. Float

Charger supplies all loads and maintains a slight charge on the battery bank.

2. Equalize

Charger supplies all loads and provides a larger current at a higher voltage on the battery bank to restore battery capacity to its maximum charge.  

Term

Where are the 250VDC battery chargers located?

 

125VDC Chargers?

 

28VDC Chargers?

Definition

460V switchgear room 84'

 

460V switchgear room 84'

 

Relay and Battery RM 100'

Term
125 VDC Battery...
Definition

3- 125VDC battery banks A,B,C

6 Battery chargers(Primary and Backup for each)

60 Cells for each Battery Bank

Location: A/B 100' Battery room and

C 64' 4KV Switchgear

Each Battery is rated for 2 hours of operation during a LOPA.

 

FEED: Control power for relays, breaker control, and indications.

Term
During a complete loss of AC power (OSP and Diesel loss) which chargers can be supplied by a portable DG?
Definition

125 VDC Backup Battery Chargers

2A2,2B2, and 2C2

1A2,1B2, and 1C2

 

28VDC Backup Battery Chargers

1A2 And 2A2

Term

125VDC system distibution has how many cabinets?

How can they be aligned?

Definition

7 cabinets of distribution.

Each cabinet can be supplied power from 2 seperate 125VDC buses through mechanical interlocked circuit breakers located in the cabinets.

The infeed breakers are designated Regular (R) and Emergency (E)

Term
125 VDC CW Distribution System...
Definition

2- 125VDC CW Battery Banks (1 per unit)

2 Spare Cells

6 Battery chargers (3 per Bank)

 

Located in the CW Switchgear building.

Term
28VDC Distribution System...
Definition

2 Battery Banks per Unit

4 Battery chargers (2 primary and 2 backup)

Powered from the EDGs in the event of a LOPA

Sized to last 2 hours in te event of a total LOPA

Location: 100' battery room shared with A/B 125VDC

 

FEED: Control power for indication and MCR control bezzels, VIB, Annunciators,

Status Panel RP4

Term

28VDC Ditribution Cabinets...

 

How can they be aligned in an accident?

Definition

4 cabinets of distribution.

Each cabinet can be supplied power from 2 seperate 28VDC buses through mechanical interlocked circuit breakers located in the cabinets.

The infeed breakers are designated Regular (R) and Emergency (E)

Term

What are the power sources for the 125VDC Battery Chargers?

 

28VDC Battery Chargers?

Definition

125VDC 2A1=2A 230V, 2A2(Backup)=2C

125VDC 2B1=2B 230V, 2B2(Backup)=2A

125VDC 2C1=2C 230V, 2C2(Backup)=2B

 

28VDC 2A1=2A 230V, 2A2(Backup)=2C

28VDC 2B1=2B 230V, 2B2(Backup)=2C

 

 

 