Term
Fuel Pool
Describe the normal/required temps of fuel pool. |
|
Definition
-Max temp is 140F. -Normally maintained <125F and cool entire pool every 12 hours. -Done for work environment, demin sysem, and clarity of the pool. |
|
|
Term
Fuel Pool
Describe heat load assumptions for fuel pool. |
|
Definition
-Noraml outage is 5600,000 btu/hr by 141 bundles every 18 months. -Emergency cooling is 19,000,000 btu/hr (full core). |
|
|
Term
Fuel Pool
Describe significant levels in the skimmer surge tanks. |
|
Definition
-Normally 5-8 feet. -High alarm at 8'. -Low alarm at 4'. -Trip pump at 2'6". |
|
|
Term
Fuel Pool
Describe pump trips alarms and capacity. |
|
Definition
-450gpm capacity. -Trip on 2'6" level in first skimmer surge tank. -Trip on 6.5# suction pressure. -Alarm on 50# discharge pressure. |
|
|
Term
Fuel Pool
Describe the heat exchanger cooling. |
|
Definition
-Shell side has RBCCW flow. |
|
|
Term
Fuel Pool
Describe the pump power supplies. |
|
Definition
-11/12 pumps MCC-133/143. -Holding pumps, precoat pump, and agitators are MCC-141. |
|
|
Term
Fuel Pool
Describe when the holding pumps start. |
|
Definition
|
|
Term
Fuel Pool
Describe the leak alarms. |
|
Definition
-Refuel bellows seal leak alarm: .75gpm. -Fuel pool gate leak alarm: 1.0gpm. -Rx well seal leak alarm: 3.0gpm. |
|
|
Term
Fuel Pool
Describe heat exchanger alarms. |
|
Definition
-120F inlet. -100F outlet. |
|
|