Term
HVAC
Describe fans with heating coils trip setpoint. |
|
Definition
|
|
Term
HVAC
Describe the stages of a typical V-AC unit. |
|
Definition
-Double inlet dampers (2 for secondary containment). -Roll-o-matic filters. -Cooling coil. -Face and bypass dampers. -Heating coil. -Temperature element. -Fan. |
|
|
Term
HVAC
Describe the purpose of the HVAC syste. |
|
Definition
-Control environmental conditions for equipment and personnel. -Controlled flow and release. -Flow path is always low areas to higher radioactive areas. |
|
|
Term
HVAC
Describe the main supply fans. |
|
Definition
-Known as the 10 fans (V-AC-10A/B). -Normally both run. -Have cooling coil trip. -Trip on loss of Rx building exhaust fans (V-EF-24A/B). -Supply lower areas in the Rx building. -Powered by MCC-111/141. -Exhaust into plenum. |
|
|
Term
HVAC
Describe the concern with a loss of the main supply fans. |
|
Definition
High steam chase temperature causing a Group I isolation. |
|
|
Term
HVAC
Describe the Rx building exhaust fans. |
|
Definition
-Know as the 24 fans (V-EF-24A/B). -Normally 1 fan runs. -Powered by MCC-111. -RWCU discharges into suction of 24 fans. -Exhaust into plenum. |
|
|
Term
HVAC
Describe normal pressure in Rx building. |
|
Definition
-Negative 0.25" H2O as compaired to atmosphere. |
|
|
Term
HVAC
Describe the normal pressure in the exhaust plenum. |
|
Definition
-Maintained at negative 0.5" H2O compaired to outside air. |
|
|
Term
HVAC
Describe the plenum exhaust fans. |
|
Definition
-(V-EF-20/21/22). -Powered by MCC-132/132/122. -Exhaust fans to Rx building vent stack. -Fans are modulated to maintain exhaust plenum pressure. |
|
|
Term
HVAC
Describe the exhaust plenum rad monitor setpoint. |
|
Definition
26mrem/hr or downscale of .1mrem/hr. |
|
|
Term
HVAC
Describe the refuel floor fans. |
|
Definition
-Known as the 4 fans (V-AH-4A/B) -Powered by MCC-132/122). -Normally only 1 fan running. -Trips on loss of refuel exhaust fan (V-EF-28). -Safety related dampers fail closed on loss of air. |
|
|
Term
HVAC
Describe the refuel floor rad monitor setpoint. |
|
Definition
50mrem/hr or downscale of .1mrem/hr. |
|
|
Term
HVAC
Describe the refuel floor exhaust fan. |
|
Definition
-Known as the 28 fan (V-EF-28). -Powered by MCC-132. -If running and 4 fan is in auto, when flow is sensed the 4 fan will start. -If lost the 4 fan will trip. -Exhaust into plenum. |
|
|
Term
HVAC
Describe the sample station exhaust fan. |
|
Definition
-(V-EF-10). -Powered by MCC-132. -Exhausts into plenum. |
|
|
Term
HVAC
Describe the rad waste vent line. |
|
Definition
-Rad waste exhaust fans. -Has 2 fans in rad waste (V-FU-1/2). -Powered by MCC-111/141. -Has heating coil trip. -Discharges into plenum. -Maintains rad waste at -0.25" H20. -Interlocked with rad waste supply fans (V-MZ-3A/B). |
|
|
Term
HVAC
Describe the cross-connect between 28 fan inlet and SBGT. |
|
Definition
-Damper opens (V-D-42) pens to connect duct on V-EF-24/28 together for SBGT operations. |
|
|
Term
HVAC
Describe the HPCI room alarms. |
|
Definition
High temp: 97F. Low temp: 65F. |
|
|
Term
HVAC
Describe Rx building temp alarm. |
|
Definition
|
|
Term
HVAC
Describe the ECCS room temp alarms and cooling supply. |
|
Definition
-100F. -SW is normal supply with ESW as b/u. |
|
|
Term
HVAC
Describe the RCIC room temp alarm. |
|
Definition
|
|
Term
HVAC
Describe the CRD pump room temp alarm and control. |
|
Definition
-Alarms at 104F. -Sw starts at 85F, second starts at 90F. |
|
|
Term
HVAC
Describe recirc MG set room fans. |
|
Definition
-(V-SF-3/4). -Powered by MCC-133/122. -Modulate to keep room at .25" H2O positive pressure. |
|
|
Term
HVAC
Describe the sludge tank vent filter unit. |
|
Definition
-Vent for RW tanks: -Condensate phase, clean-up phase, spent resin, waste sludge. |
|
|
Term
HVAC
Describe the SJAE fan. |
|
Definition
-Known as the 26 fan (V-EF-26). -Suctions from SJAE room exhaust to plenum and dilution air for SBGT. -Normally runs. -Powered by MCC-132. -On SBGT initiation damper to SBGT isolates and directs to plenum. |
|
|
Term
HVAC
Describe the cond/demin MVP room fan. |
|
Definition
-Known as the 11 fan (V-EF-11). -Powered by MCC-132. -Normally runs. -Suctions from cond/demin MVP room and exhausts to plenum or SBGT dilution air. -SBGT initiation damper isolates to SBGT and aligns to plenum. |
|
|
Term
HVAC
Describe the turbine building fans. |
|
Definition
-(V-AH-1/2). -Neither fan normally ran. -Powered by MCC-121/142B. -Both start when ceiling temp reaches 250F. -At -0.2"H2O in plenum the fans trip and plenum room ceiling dampers shut. |
|
|
Term
HVAC
Describe the EDG fans. |
|
Definition
-(V-SF-9/10). -Powered by 12EDG/11EDG. -Start when EDG start signal or when bus is energized. -EDG building suction dampers open then discharge shut and vice versa. |
|
|
Term
HVAC
Describe the recombiner building exhaust fans. |
|
Definition
-(C-1004A/B). -Located in MVP room. -Discharge to plenum. -Fans trip on exhaust plenum press of -0.2"H2O. |
|
|