Term
HWC
Describe the HWC trips and setpoints. |
|
Definition
-Main steam flow: <30%. -11 or 12 AE trip: AO-1085A/B closed. -Total H2 flow high: >58scfm. -Either RFP H2 flow high: >24scfm. -Low O2 pressure: <45psig. -Area H2 monitors: >1% H2. -O2 concentration at recombiner outlet: <5%. -Both recombiner outlet valves closed: AO-7557A/B shut. -Manual trip from control room or local at C-308. |
|
|
Term
HWC
Describe the HWC and RFP interlock. |
|
Definition
-If RFP secured or its recirc valve is open then that trains supply valve (CV-4152A/B) will shut. |
|
|
Term
HWC
Describe the gas compressor start signals. |
|
Definition
-H2 tank pressure at 110psig with the pump not operating and H2 receiver <2000psig. -H2 receiver <1800psig, with pump not running, and tank pressure >80psig. |
|
|
Term
HWC
Describe when the H2 pump starts. |
|
Definition
Cycles between 1200 to 1900 psig. |
|
|
Term
HWC
Describe the pump trips. |
|
Definition
-High receiver pressure (1900#). -Pipe line low temp: -250F. -Relief valve open: Tailpipe at -40F. -Low N2 purge or system pressure. |
|
|
Term
HWC
Describe O2 supply on loss of normal supply. |
|
Definition
-O2 bottles available. -That will ensure enough O2 available for complete H2 recombination of H2 remaining in system after trip. |
|
|
Term
HWC
Describe what happens on system trip. |
|
Definition
-Pretty much all valves close. -O2 supply flow to recombiners (primary and backup) take 12 minutes to close to ensure enough to recombine the H2. -All others close immediately. |
|
|
Term
HWC
Describe the O2 tank high pressure relief. |
|
Definition
-250psig. -Vented to atmosphere. |
|
|
Term
HWC
Describe any time delays in HWC. |
|
Definition
-Injection of O2 is delayed based on Rx power. -At 100% roughly 45 seconds to allow time for the H2 to show up at the O2 injection point. |
|
|
Term
HWC
Describe the steam flow interlock. |
|
Definition
H2 is interlocked to prevent injection when steam flow is <30%. |
|
|
Term
HWC
Describe rad levels and protection with HWC. |
|
Definition
-Rad levels in steam areas can increase by 3 to 5 times with an increase in H2 injection rate. -Can reduce HWC injection for work if will save 1 rem and have shift supervision permission. -Unplanned lowering takes Plant Manager permission. |
|
|
Term
HWC
Describe RWCU relationship with HWC. |
|
Definition
-Maximize RWCU flow 24 hours prior to HWC injection reduction and maintain until 72 hours after HWC restored to normal injection rate. |
|
|