Term
Air/N2
Describe the power supplies to the compressors and effects on loss/return of power. |
|
Definition
-15 compressor is LC-103. -Load shed on loss of power, does not return. -16 compressor is LC-107. -Not load shedded but does not restart. -17 compressor is LC-108. -Not load shed, will restart upon return of power. |
|
|
Term
Air/N2
Describe the instrument N2 to instrument service air auto transfer. |
|
Definition
-Will auto transfer to air if get to 110# high or to 99# low. -Normal band is 102# - 107#. |
|
|
Term
Air/N2
Describe applicable pressure functions. |
|
Definition
-90#: Auto reset and reopening of non-essential instrument air isolation valves. -85#: Instrument low pressure alarm. -82#: Service air header low pressure and service air isolation valve closes (reopens at 95#). -80#: Non essential instrument air isolation. -75#: FRV lockup and low flow valve fails open. -60#: Scram air header low pressure, rods drift in (SCRAM). -50#: MSIVs drift close. -45#: SCTMT isolation dampers in Rx building start to shut. -15#: HVAC units shut down due to loss of damper control air. |
|
|
Term
Air/N2
Describe the receiver relief setpoint. |
|
Definition
|
|
Term
Air/N2
Describe what Alt N2 supplies. |
|
Definition
-A train: B/U supply to t-ring seals, TORUS vacuum breakers, and 3 SRVs. -B train: B/U supply to t-ring seals, inboard MSIV actuators, 3 SRVs, and hard pipe vent isolation valves and rupture discs. |
|
|
Term
Air/N2
Describe the normal pressure for Alt N2. |
|
Definition
-Normally 95-97 psig. -Alarm at 91 psig. |
|
|
Term
Air/N2
Describe the Alt N2 pressure requirements. |
|
Definition
-Required to be > than 410psig. -Alarm at 200 psig and system isolates itself. |
|
|