Term
Power Requirements : Most Controller |
|
Definition
120 Volt Single Phase 3 Amp Electrical Power
|
|
|
Term
Maximum Distance from Controller to Last Control Valve |
|
Definition
|
|
Term
Power Requirements >7.5 HP |
|
Definition
|
|
Term
Power Requirements <7.5 HP |
|
Definition
120-230 Volt Single Phase |
|
|
Term
|
Definition
1.Antisiphon a.Atmospheric Vaccum Breaker b.Pressure Vaccum Breaker 2.Back Pressure Devices a.Double Check Valve b.Reduced Pressure Backflow Device |
|
|
Term
|
Definition
Used in most 4" Wells Pump is below the water level low flow and high pressure characteristics Don't need to be primed. Only push water, don't pull it.
|
|
|
Term
Horizontal Centrifugal Pump |
|
Definition
|
|
Term
|
Definition
|
|
Term
|
Definition
Used to increase pressure in a pressurized supply line |
|
|
Term
|
Definition
|
|
Term
|
Definition
|
|
Term
A Looped main reduces demand by____ at the farthest point. |
|
Definition
|
|
Term
Maximum velocity of water in an irrigation system |
|
Definition
|
|
Term
|
Definition
Class=wall thickness Schedule=160 thin walls.. offer value 40=heavy walled, used in pressurized lines. |
|
|
Term
|
Definition
|
|
Term
Factors used in determining irrigation requirements |
|
Definition
|
|
Term
|
Definition
Static pressure minus friction losses |
|
|
Term
Operating Pressure for Drip |
|
Definition
|
|
Term
Operating Pressure for Sprays |
|
Definition
|
|
Term
Operating Pressure for 35' Rotors |
|
Definition
|
|
Term
Operating Pressure for 50' Rotors |
|
Definition
|
|
Term
Disc Meter Size and Volume Residential |
|
Definition
5/8" meter=12 GPM 3/4" meter=18 GPM
|
|
|
Term
Disc Meter Size and Volume Commmercial |
|
Definition
1"=28 GPM 1.5"=50 GPM 2"=80GPM
|
|
|
Term
Large scale sites with Turbine type meter |
|
Definition
2"meter= 120 GPM 3" meter= 280 GPM |
|
|
Term
Maximum percent of flow capacity a meter should be expected to meet |
|
Definition
80% Therefore if a meter is rated at 50GPM only zone for 37 GPM. |
|
|
Term
|
Definition
Required on all irrigation controllers in Florida |
|
|
Term
Application of rate of properly spaced spray nozzels (8',10'12',15'radius) |
|
Definition
|
|
Term
Typical Rotor nozzle application rate for 20',25',35',50' radius... |
|
Definition
|
|
Term
|
Definition
loss of pressure as water moves through a pipe. |
|
|
Term
Increased Velocity of water has what effect on pressure loss? |
|
Definition
It(pressure loss) increases as velocity increases. |
|
|
Term
Factors that cause pressure loss |
|
Definition
length of pipe number of fixtures velocity of water
|
|
|
Term
locations to use low angle nozzles |
|
Definition
anywhere that wind may be a problem. |
|
|
Term
End Suction Centrifugal Pump |
|
Definition
Great at pushing water Suck at sucking it. Good when water source is higher than pump. Generally need to be primed the first time. water typically enters the pump through a "suction inlet "centered on one side of the pump, and exits at the top.
|
|
|
Term
|
Definition
|
|
Term
|
Definition
|
|
Term
|
Definition
simply a submersible pump or a turbine pump that is attached to the bottom of a float. in a pond or lake much easier to install than a standard submersible, jet-pump, or turbine much more energy efficient than an end-suction centrifugal Floating fountains and pond aerators are another utilization of floating pump technology
|
|
|
Term
|
Definition
the water pressure when measured with all water flows shut off; no faucets running, ice maker is off, no sprinklers on, nobody taking a shower |
|
|
Term
Reduced Pressure Backflow Preventer |
|
Definition
the standard for commercial irrigation installations made for high-hazard uses The R.P. Unit must be installed 12 inches (300mm) above ground
|
|
|
Term
Dual check backflow preventers |
|
Definition
|
|
Term
Double Check Backflow Preventer |
|
Definition
will ALWAYS have two manual valves, one on the inlet and one on the outlet manual valves are used as emergency shut-offs and are also necessary to properly test the operation of the backflow preventer will also have test cocks (small outlets sticking out of the side of the backflow preventer) for connecting to test gauges AWWA (American WaterWorks Assoc.)"double checks may be used for sprinkler irrigation systems, provided no chemicals are injected into the sprinkler water"
|
|
|
Term
|
Definition
you only need to install one of them and it is installed on the mainline leading to the control valves Like the AVB it must also be installed above ground and it must be 6 inches (150mm) higher than the highest sprinkler head or drip emitter controlled by any of the valves.
|
|
|
Term
Atmospheric Vacuum breaker |
|
Definition
the least expensive backflow preventer AVB is installed on the pipe right after the control valve. for backflow prevention you must install one AVB after EVERY control valve, no exceptions It must be installed at least 6 inches (150mm) higher than the highest sprinkler head, bubbler, or drip emitter outlet that is turned on and off by that control valve
|
|
|
Term
|
Definition
a manual or automatic control valve with a built-in atmospheric vacuum breaker Like the AVB it must be installed 6 inches higher than the highest sprinkler head or drip emitter outlet. Anti-siphon valves are the most common type of backflow preventer used on residential irrigation systems Never install a anti-siphon valve upstream of any other valve Anti-siphon valves should never be installed below ground
|
|
|