Term
Function of Liquid Rad Waste System |
|
Definition
Collect, process, reclaim, or dispose of radioactive waste such that the discharge of the radioactive waste to the environment will be limited. |
|
|
Term
Drywell drains associated with identified leakage |
|
Definition
|
|
Term
Drywell drains associated with unidentified leakage |
|
Definition
|
|
Term
Discuss RHR Pump Room floor drains |
|
Definition
Provided with orifices to limit the amount of back flooding into these rooms in the event the torus area gets flooded or one of the RHR Pump Rooms becomes flooded. |
|
|
Term
Drywell Floor Drain Sump Monitoring system operability |
|
Definition
Either the flow or level monitoring portion of the system must be operable. The system consists of a sump discharge flow integrator, one sump level recorder, and one sump fill rate computer point (rate of change). The drywell floor drain sump monitoring system is operable whenever one of these channels is operable. |
|
|
Term
"Action, per B.07.01-05, to be taken if TB Equip drain sump becomes contaminated." |
|
Definition
"Place HS-2562, COND DRIP TANK TO HOTWELL, in the COLL (collector) position. This action sends TB equip drain sump to rad waste." |
|
|
Term
Precaution associated with sending DW Equip drain sump to the waste collector tank. |
|
Definition
"Due to elevation head, water hammer during pump discharge check valve slam has ruptured the rupture disk inside the drywell." |
|
|
Term
Precaution associated with DW Floor drain sump pumps |
|
Definition
"When placed in run, will not auto stop upon reaching low level trip setting and thus requires continuous monitoring." |
|
|
Term
Expected auto start and trip of DW Floor drain sump |
|
Definition
Auto start: 8.6-9.0 inches; Auto trip: 2.2-2.6 inches |
|
|
Term
DW Equip drain sump pump power supplies |
|
Definition
|
|
Term
RX Build equip drain sump pump power supply |
|
Definition
|
|
Term
Cond drip tank pump power supplies |
|
Definition
|
|
Term
DW Floor drain sump pump power supplies |
|
Definition
|
|
Term
RX Build floor drain sump pump power supplies |
|
Definition
|
|
Term
TB Floor Drain and TB Norm Waste sump pump power supplies |
|
Definition
Both have MCC-131 and MCC-121 |
|
|
Term
Liquid Radwaste Normal flow line-up |
|
Definition
Recycle: Pump from waste collector tank and floor drain collector tank, through waste collector filter, back to tanks. |
|
|
Term
Liquid Radwaste make-up to CSTs flow path |
|
Definition
From waste collector tank and floor drain collector tank, through waste collector filter, through waste demineralizer to waste sample tanks (2) or floor drain sample tank where the water is sampled. Once the determination that the water is clean is made, it is sent to CSTs. |
|
|
Term
Which Scram Discharge Volume does RB Equip Drain Tank receive? |
|
Definition
East Scram Discharge Volume (Equip = East) |
|
|
Term
Which Scram Discharge Volume does RB Floor Drain Tank receive? |
|
Definition
West Scram Discharge Volume |
|
|
Term
DW Equip and Floor drain system response to Group II primary containment isolation |
|
Definition
Isolation valves close which trips the pump REGARDLESS of mode. |
|
|
Term
What determines whether condensate drip tank is sent back to main condenser or waste collector tank? |
|
Definition
"Sent to main condenser if condensate drip tank discharge pressure greater than 10 psig (indicates pump running) and conductivity less than 1 micro-mho. Otherwise, sent to waste collector tank." |
|
|
Term
Which drywell drain sump has a heat exchanger? |
|
Definition
Drywell equipment drain sump |
|
|
Term
What happens if drywell equip drain sump reaches 140 degrees F? |
|
Definition
AO-2560A closes and AO-2560B opens to send water through heat exchanger and back to sump. Resets when temperature goes below 140 degrees F. |
|
|