Face velocity of a return grille should be limited to
Definition
400 fpm
Term
If a packaged heat/cool unit is equipped with an economizer
Definition
provide "free cooling" on certain days of the year
Term
Face velocity of a supply register should be?
Definition
500 to 700 fpm
Term
When installing an economizer it is important to check
Definition
that the vanes do not bind during operation
Term
you just finished installing a 60,000 btuh output gas furnace and now you need to determine the volume of air that is flowing out of this furnace. you measure the supply temperature to be 105 F and the return temperature to be 68 F. What is the CFM at the bonnet
Definition
1500 CFM
Term
The sensible heat equation can be used to determine air flow in which of the following systems
Definition
fossil fuel heating
Term
a manufacturer recommends a temperature rise between 35F and 55F. You have a temperature rise of 60F. How should you resolve this?
Definition
increase the blower speed
Term
what could cause a higher than recommended temperature rise over a furnace
Definition
a clogged air filter
Term
once a gas piping system has been assembled it should be pressure tested with
Definition
compressed air
Term
a piping system that is pressurized with natural gas should be leak tested with
Definition
an electronic leak detector and/or soap bubbles
Term
electronic leak detectors are calibrated in
Definition
ppm
Term
what type of soap solution should be used to check for gas leaks?
Definition
one specifically designed for that purpose
Term
which of the following is a diaphragm type differential pressure gage
Definition
magnehelic
Term
a differential pressure gage reads pressures that are
Definition
differential or relative to atmosphere
Term
a high supply side static pressure is an indication of
Definition
a clogged evaporator coil
Term
a high return side static pressure is an indication of
Definition
a dirty air filter
Term
why do you cross break ductwork
Definition
to add strength and rigidity
Term
a duct traverse yields
Definition
the average CFM based on the average velocity multiplied by the square feet of duct
Term
a direct drive blower wheel with damaged or missing vanes can cause
Definition
loss of air flow, motor damage and noise
Term
during a PM call on a gas furnace you find loose and corroded wires. What, if anything, should be done?
Definition
retighten all loose wires and replacethe corroded portions of the wires
Term
when preparing to perform an air balancing procedure
Definition
all volume dampers should be open, the blower should be adjusted to the desired speed, and the air filter should be cleaned or replaced
Term
which of the following should be included in an air balancing report
Definition
supply, return, and total static pressure
Term
in a trunk and branch duct system, trunk velocity should be kept between
Definition
700 to 900 fpm
Term
horizontal runs of flexible duct should be supported every
Definition
5 feet
Term
minimum strap width for hanging flexible duct is
Definition
1 1/2"
Term
maximum sag for horizontal runs of flexible duct is
Definition
1/2" per foot
Term
ductwork installed in unconditioned spaces should be
Definition
insulated
Term
ducts installed in damp crawl spaces should be
Definition
wrapped with insulationand wrapped with a vapor barrier
Term
human comfort can be defined in terms of
Definition
dry bulb temperature, relative humidity, and air velocity
Term
The proper manifold pressure for natural gas is
Definition
3.2" to 3.8" of water column
Term
the proper manifold pressure for LP gas is
Definition
11" to 13" of water column
Term
inlet pressure to a gas valve should never exceed
Definition
14" of water column
Term
in a combination gas valve
Definition
the pilot valve is in series with the main valve
Term
a two stage gas valve has?
Definition
two pressure regulators and two main valves
Term
manometers used to measure gas pressure are calibrated in
Definition
inches of water column
Term
when reading a u-tube manometer
Definition
the columns are added
Term
one psig is equal to
Definition
27.72" of water column and 2.3' hd.
Term
the older mechanical thermostats and the newer electronic thermostats
Definition
are made to be compatible
Term
which of the following thermostat types can be programmed for a different time schedule each day of the week
Definition
7 day programmable
Term
to choose the proper air cleaner for a given application you must know?
Definition
the volume of return air
Term
which of the following would be used to delay the off time for a blower
Definition
delay on break relay
Term
which of the following is a category I furnace?
Definition
83% AFUE
Term
venting a two pipe condensing furnace through the roof requires a maximum separation of the two pipes of
Definition
18"
Term
when horizontally venting a condensing gas furnace be sure to
Definition
maintain a 12" separation between the inlet and the outlet of the two pipoes
Term
when venting a category IV furnace what is the minimum separation from the vent pipe discharge to a forced air inlet into the building
Definition
3 feet
Term
relative to combustion air a confined space is defined as
Definition
an area with less than 50 ft^3 of volume for each 1000 btuh of input for all appliances in that area
Term
what is the required volume of air to sustain combustion?
Definition
50 ft^3 per 1000 btuh input
Term
combustion air can be supplied to a confined space by
Definition
one opening within 12" of the floor and one opening within 12" of the ceiling
Term
in venting tables for category I furnaces the "Vent Height" can be defined as
Definition
the distance from the outlet of the draft diverter to the chimney cap
Term
the primary heat exchanger is typically made of
Definition
aluminized steel
Term
the secondary heat exchanger is typically made of
Definition
stainless steel
Term
a counterflow furnace installed in a closet must be mounted on
Definition
a combustible floor base
Term
what else is important with regard to a closet installation of a two pipe 90% furnace in a residence
Definition
Noise transmission
Term
an attic installation of a horizontal gas furnace requires
Definition
the use of a zero clearance furnace or a non-combustible mounting base
Term
on a call for heat with an induced draft furnace, which of the following is the next event in the sequence of operation
Definition
draft inducer is energized
Term
on a no heat call you find the following: R to W is made, The inducer is running, no main burner. What is most likely the cause of these symptoms?
Definition
A pressure switch stuck closed
Term
on a call for heat the integrated circuit board will check for which of the following before energizing the draft inducer?
Definition
An open pressure switch
Term
what device proves that the inducer motor is running and that the venting system is not obstructed
Definition
pressure switch
Term
on a call for heat, after the pressure switch closes the next event is
Definition
HSI is energized
Term
on a call for heat, after the HSI is energized the next event is
Definition
main burner circuit is energized
Term
on a call for heat, after the main burner is energized the next event is
Definition
flame is proved
Term
on a call for heat, after the flame is proven the next event is
Definition
blower motor is energized
Term
the products of complete combustion include
Definition
co2, nitrogen, water vapor, and heat
Term
primary combustion air
Definition
is mixed with the gas in the venturi before ignition
Term
secondary combustion air
Definition
is supplied to the burner after ignition to sustain combustion
Term
too much primary air can cause
Definition
the flame to lift off the burner
Term
which of the following produces a hard, noisy blue flame
Definition
in-shot burner
Term
ribbon burners must be properly aligned
Definition
to insure proper flame carry-over
Term
modern residential gas burners are made from
Definition
sheet metal
Term
which ignition system is de-energized once the main burner flame is established
Definition
interrupted
Term
the pilot flame must envelope how much of the thermocouple
Definition
3/8" to 1/2"
Term
a thermopile generates
Definition
750 DC mV
Term
the ACCA manual used to perform residential load calculations is
Definition
Manual J
Term
AFUE can be calculated by
Definition
useful output/input
Term
a large difference between the wet bulb and the dry bulb temperatures is an indication of
Definition
low relative humidity
Term
which of the following is used to measure RH%
Definition
sling psychrometer