Term
OG
Describe the function of the preheater. |
|
Definition
-Adds an addition 50F of superheat to offgas before getting to recombiner. -Prevents condensation in the recombiner and wetting the catalyst. -Uses main steam from the SJAE supply line at 260#. |
|
|
Term
OG
Describe the state of the gas at the preheater. |
|
Definition
-Enters at low pressure (alarm at 19.5#). -Leaves at 370F (alarm at 270F). |
|
|
Term
OG
Describe where preheater condensate goes. |
|
Definition
-Condensate produced in the preheaters shell side is collected in the hotwell and discharged to the condensate flash tank. -Has a high level alarm at 3/4. |
|
|
Term
OG
Describe dilution steam. |
|
Definition
-Yields H2 at <4% by volume. -Keeps recombiner <850F. -Main Steam that taps off of the A & B steam lines. |
|
|
Term
OG
Describe the minimum operating temperature of the catalyst. |
|
Definition
|
|
Term
OG
Describe the electric heaters for the recombiners. |
|
Definition
-Mounted at bottom of recombiner right after the preheater. -Cycle at wall temp of 300-350F. -Keeps catalyst bed >212F. |
|
|
Term
OG
Describe the recombiner effluent. |
|
Definition
-Wet high temp (500F) leaves recombiner and enters desuperheating condenser. -Cooled by condensate water and steam is collected in hotwell. -Dry cool off gas (115F) goes to 42" delay line. |
|
|
Term
OG
Describe the condensate flash tank. |
|
Definition
-Seperates high temp from low temp influents to tank by allowing high temp influents to flash to steam at low press (8psia). -Vents flashed vapor to main condenser. -Low temp influents drain to Drain Cooler. |
|
|
Term
OG
Describe the Drain Cooler. |
|
Definition
-Reduces condensate flash tank drain temps before returning them to main condenser. -Cooled by main condensate. |
|
|
Term
OG
Describe H2 & O2 analyzer. |
|
Definition
-Draws suction from upstream of AO-7557A/B on discharge of desuper condenser. -Sampling is returned to main condenser. |
|
|
Term
OG
Describe the H2 & O2 analyzer alarm and trips. |
|
Definition
-Any 1 of 3 analyzers can cause alarm. -Alams at >2%. -2 of 3 >4% and AO-7557A/B open and 10 seconds cause off gas compressor to trip. |
|
|
Term
OG
Describe what instrument air does. |
|
Definition
-Provides enough O2 for recombination. -Purge recombinber after shutdown. |
|
|
Term
OG
Describe pretreatment rad monitoring. |
|
Definition
-Gives alarm and terminates off gas flow for high rad. -2 of 2 logic. -2 high, 2 low, 1 high 1 low, trips. -Starts 30 minute timer and after timer off gas flow is terminated by shutting (AO-7557A/B) Desup condenser outlet and (AO-1085A/B) intercondenser outlet. -These valves fail closed on loss of air. |
|
|
Term
OG
Describe the desuperheating condeser high temp alarm and what happens. |
|
Definition
-170F. -Shuts condenser outlet valve (AO-7557A/B). |
|
|
Term
OG
Describe air ejector low steam pressure trip. |
|
Definition
-If less than 110# for 5 seconds at 2nd stage nozzle will shut inter condenser outlet (AO-1085A/B) and desuper condenser outlet (AO-7557A/B). |
|
|