Term
RCIC
Describe the RCIC initiation. |
|
Definition
-Initiated at low-low Rx water level (-47"). -Uses 1 out of 2 taken twice logic. |
|
|
Term
RCIC
Describe the RCIC PCIS isolation signals and what is isolated. |
|
Definition
-Group V isolation signals. -60# in discharge header. -44,434lbm/hr flow rate. -187.5F area temp. -Isolates the RCIC steam supply inboard (MO-2075) and outboard (MO-2076) valves. -Trips the trip throttle valve (MO-2080). |
|
|
Term
RCIC
Describe where RCIC steam is supplied from. |
|
Definition
|
|
Term
RCIC
Describe where RCIC water flow goes. |
|
Definition
To Rx through the A feed line. |
|
|
Term
RCIC
Describe the RCIC design flow. |
|
Definition
Able to deliver design flow of 400gpm to Rx vessel within 30 seconds of initiation at pressure range of 165-1135#. |
|
|
Term
RCIC
Describe the RCIC pump suction trips. |
|
Definition
-70# high trip. -15"HG low trip. |
|
|
Term
RCIC
Describe the minimum flow valve operation. |
|
Definition
-Air powered that fails open on loss of air/power. -Two position switch operates. -If in OPEN position then: -Valve is open when <80gpm total flow. -Valve is closed when >80gpm total flow. -In AUTO position the valve is closed if there is: -No ititation signal. -Turbine steam supply (MO-2078) is closed. -Turbine trip throttle valve (MO-2080) is not full open. -And flow is > 40gpm. |
|
|
Term
RCIC
Describe the RCIC pump suctions. |
|
Definition
-Normally the CST. -TORUS is alternate. |
|
|
Term
RCIC
Describe the pump suction supply interlocks. |
|
Definition
-If CST level reaches 2'8" then an open signal is given to the TORUS suction valves (MO-2101/2100). -When TORUS suction valves are full open then a close signal is given to CST suction valve (MO-2102). |
|
|
Term
RCIC
Describe the RCIC test line valve interlocks. |
|
Definition
-If either TORUS suction valve (MO-2101/2100) is open then a closed signal is shut to the RCIC test return isolation valves (MO-2110/3502). -This is done to prevent diverting water meant to go to the vessel to going back to the CSTs. |
|
|
Term
RCIC
Describe the RCIC steam trap valve interlocks. |
|
Definition
-If the turbine steam supply valve (MO-2078) is open (opens on RCIC initiation signal) then the steam trap drains to the cond (CV-2082A/2082B) shut. |
|
|
Term
RCIC
Describe when the RCIC water side injection valves open. |
|
Definition
-Inboard (MO-2107) and outboard (MO-2106) (both DC) open on RCIC initiation signal. |
|
|
Term
RCIC
Describe the turbine trip throttle valve (MO-2080) trips. |
|
Definition
-Exhaust pressure of 125# instantaneous. -Exhaust pressure of 50# for 5 seconds. -Pump suction of 15"Hg. -Group V isolation. -Manual trip. -Overspeed of 5625 RPM requires manual reset. |
|
|
Term
RCIC
Describe steam supply valve operation from Rx on initiation. |
|
Definition
-Both inboard (MO-2075) and outboard (MO-2076) are normally open. -Only the outboard gets an open signal on initiation. -Inboard AC outboard DC. |
|
|
Term
RCIC
Describe the turbine steam inlet valve (MO-2078) alarms. |
|
Definition
-If turbine steam inlet valve (MO-2078) is 25% (or greater) open for 15 seconds with flow < 40gpm then actuates an alarm. |
|
|
Term
RCIC
Describe cond pump discharge path and interlocks. |
|
Definition
-If stam supply inlet valve (MO-2078) is open then the discharge valves (CV-2849/2848) to CRW are shut. -Cond pump discharge is then directed to the RCIC pump suction. |
|
|
Term
RCIC
Describe where RCIC non-condensibles are discharged to. |
|
Definition
-Discharged to the TORUS air space. -This is an oxygen concern. |
|
|
Term
RCIC
Describe where RCIC lube oil gets cooling. |
|
Definition
-16gpm is diverted from RCIC pump discharge to the lube oil cooler. |
|
|
Term
RCIC
Describe RCIC exhaust overpressure protection. |
|
Definition
-RCIC trip if 125# instantaneously or 50# for 5 seconds. -Two rupture discs in parallel. -Discs rupture at 150+/- 10# and discharge to RCIC room. -Alarm at 5# to detect leakage past first rupture disc. |
|
|
Term
|
Definition
-5 stage single suction double volute pump. -Flow of 416gpm. -400gpm to Rx vessel. -16gpm to lube oil HX and condenser. -Discharge is at the center of the pump. |
|
|
Term
RCIC
Describe the lube oil alarms. |
|
Definition
-Low pressure at 4#. -High temperature at 150F. |
|
|
Term
RCIC
Describe RCIC flow and time to speed. |
|
Definition
Will deliver rated flow of 400gpm in 30seconds. |
|
|
Term
RCIC
Describe RCIC flow control. |
|
Definition
-Flow controller, ramp generator, and flow indication are powered by Y-70. -Governor in standby is set to reach about 2000rpm. -Trip throttle valve is normally open and steam supply valve is normally closed. -Ramp generator starts when trip throttle valve and steam supply valves are not fully closed. -If Y-70 is lost, RCIC will stay at minimum speed of 2150rpm. |
|
|
Term
RCIC
Describe the turbine oil pump. |
|
Definition
Oil pump driven by turbine. |
|
|
Term
RCIC
Describe the RCIC trips. |
|
Definition
-Overspeed of 5625rpm: trips TTV. -Exh press of 125# or 50# for 5 seconds: trips TTV. -Low pump suction of 15"Hg: trips TTV. -Group V isolation: trips TTV. -Manual: trips TTB. -Rx high water level +48": trips SSV. -SSV = steam supply valve to turbine. |
|
|
Term
RCIC
Describe affect on RCIC at +48". |
|
Definition
-Steam supply to turbine (MO-2078) and lube oil cooling supply (MO-2096) close. -Cond pump discharge to CRW valves (CV-2848/2849)open. -Resets at -47" and opposite happens. |
|
|
Term
RCIC
Describe what happens on RCIC initiation. |
|
Definition
-Outboard steam isolation (MO-2076) opens. -CST suction (MO-2102) opens. -Cooling water to condenser and lube oil (MO-2096) opens. -Steam supply to turbine (MO-2078) opens. -Steam supply to turbine (MO-2078) and TTV (MO-2080) not being full shut starts ramp generator. -Steam supply to turbine (MO-2078) open causes steam trap drains (CV-2082A/2082B) to shut. -Test return to CST (MO-2110/3502) shut. -Vacuum pump starts. -Steam supply to turbine (MO-2078) open causes cond pump disch to RW valves (CV-2848/2849) to shut and align discharge to RCIC pump suction. -Min flow valve (MO-2104) opens. -Injection to A feed valves (MO-2106/2107) open. |
|
|
Term
RCIC
Describe where low low water level signal comes from for RCIC. |
|
Definition
Core spray relay contacts. |
|
|
Term
RCIC
Describe RCIC logic power and affects of losses. |
|
Definition
-Powered by Div I and II. -Loss of Div I causes loss of: -Remote tripping of RCIC. -Auto initiation. -High water trip. -Loss of Div II causes loss of: -High water trip. |
|
|
Term
RCIC
Describe power to RCIC AOPs. |
|
Definition
-125Vdc and Instrument air. -Loss of air causes all AOPs to fail closed, except minimum flow line valve (CV-2104). |
|
|
Term
RCIC
Describe RCIC valve power supplies. |
|
Definition
-All valves are DC by D311, except the inboard steam isolation (MO-2075) for containment. |
|
|
Term
RCIC
Describe power supplies for the cond pump and vacuum pump. |
|
Definition
|
|
Term
RCIC
Describe pressure/level control concerns for RCIC. |
|
Definition
Cannot perform pressure/level control when suction is aligned to the TORUS. |
|
|