AB-SG-0001 Steam Generator Tube Leak
(Rev. 27)
Entry Conditions:
Chemistry department sample results
R40 rising activity, warning, or alarm (polisher)
R15 rising activity, warning, or alarm (air removal)
R19 rising activity, warning, or alarm (blowdown) not accurate following trip – don’t use as sole basis for entry
R53 rising activity, warning, or alarm (N16 detector, ≥25%)(used to verify R19 trends)
R46 rising activity, warning, or alarm (Main Steam Line High Rad)
Continuous Action Summary:
SG level rises uncontrollably – Trip | Confirm | SI | EOP-TRIP-1
If RCS >350°F and PZR level can not be maintained >17% or VCT level >4% (avoids swapover and the use of ESF equipment), Trip | Confirm | SI | EOP-TRIP-1. (Leak exceeds VCT m/u of ~70 gpm)
If R15, R19, or R53 indicates rising trend, notify RadPro to initiate primary to secondary leak response procedure.
If any R53 goes into alarm, then initiate Attachment 2
Action Levels
I. LR is ≥30 gpd but <75 gpd – shutdown not req’d – sample and trend
II. LR is ≥75 gpd sustained for ≥1 hr, but at a rate of ≤30 gpd per hr – Mode 3 in ≤24 hrs
III. LR is ≥75 gpd and at a rate of ≥30 gpd per hr – reduce Pwr to ≤50% in 1 hr & Mode 3 in next 2 hrs. LR is ≥140 gpd – Mode 3 in ≤6 hrs
If R40 alarms ‘high’, evacuate Condensate Polisher Building until RADPRO posts area.
IF SG pressure reaches 1035 to 1040 psig, AND secondary systems are available, THEN OPERATE affected MS-18, as necessary, until affected SG pressure is ≤1000 psig.
Subsequent Actions: (shutdown – isolate affected SG – cooldown – depressurize)
De-energize TGA and CP sumps
If PZR level is lowering, shift to a centrifugal charging pump and minimum letdown. If level continues to drop - Trip | Confirm | SI | EOP-TRIP-1.
If in Mode 4, initiate a shutdown to Mode 5.
If in Mode 1, 2, or 3 and PZR level is stable, identify the affected SG (prevents removal of unaffected heat sinks).
Maintain Pressurizer Level >35% to ≤70%. ensures letdown doesn’t isolate during a trip and to maintain adequate level during the RCS cooldown to 503˚F CET Temperature
Reduce flow from affected SG:
If on Steam Dumps or RHR – set unaffected MS10s to 1015 psig
If on MS10s – set unaffected MS10s to current SG pressure
Set affected MS10 to 1045 psig(ensures unaffected SGs are used for heat removal and minimize contamination via the hotwells).
Shut affected GB4, MS7 and MS18 and MS45 (23 AFW Pump inoperable, T/S 3.7.1.2). Align BD sampling to waste and isolate affected MS sample point. (Open 1WD900 and close 901)
Notify Chemistry to sample (at least once per hour) and determine leak rate until stable (≤10% rise in an hour), and Rad Pro to perform surveys.
Initiate an RCS water inventory balance and either isolate GBD or align to condenser.
Small leak w/ rising trend of ≥30 gpd/hr è shutdown to Mode 3
At 20% Rx power, Trip the Turbine then Trip the RX, complete actions through EOP-TRIP-2, then return to this AB (unless EOP-STGR is warranted) Rapid borate for 35 min for each stuck rod coming back to this procedure from EOP-TRIP-2.
Depressurize RCS to 1900 psig1 and Block Low Pressure SI possible reduction of SDM due to dilution from SG water
Isolate affected S/G
Maintain affected SG level >9% NR until in Mode 5 keep tubes covered
Cooldown RCS to 503°F as indicated by the Hottest CET, at 25° to 50°F/hr using intact Steam Generators adequate SDM only to 500°F
DEPRESSURIZE the RCS concurrently with cooldown AND MAINTAIN 20 to 40°F subcooling
WHEN the Hottest CET is at 503°F, DEPRESSURIZE RCS to the affected Steam Generator pressure
Attachment 6 – Special Considerations
Maintain affected loop RCP in operation until <200°F (aids in cooldown of S/G)
Depressurizing RCS to ≤ affected S/G pressure may result in SDM lowering due to backfill (dilution)
Cooldown and depressurize following shutdown can be completed by any of following methods:
Backfill
Drain & refill
Steaming S/G to condenser
Steam via MS10 (least desirable due to unmonitored release to environment)
When affected Steam Generator level reaches 62% NR, AFW should be secured and Steam Generator level should be allowed to drain to 9% NR before AFW is re-established.
Notes:
Small leaks – Na24 and/or I133
Large leaks – I134
2R53 warning setpoint of ~23 cpm is equivalent to a 5 gpd leak at the bottom, tube sheet area, of the steam generator at 100% power
1The preferred order for depressurizing the RCS is using the master controller, manual operation of either PS1 or PS3, aux spray, then PR1 or PR2.
End up:
GO TO IOP-6, Hot Standby to Cold Shutdown, AND INITIATE the following procedures as required:
S2.OP-SO.CN-0004(Z) Condensate System Cleanup
S2.OP-SO.GBD-0001(Q) Draining the Steam Generator
SC.RE-ST.ZZ-0002(Q) Shutdown Margin Calculation, prior to cooldown below 500°F Tave
|