Shared Flashcard Set

Details

Simulator
IOP-5
9
Other
Professional
09/29/2013

Additional Other Flashcards

 


 

Cards

Term

 

IOP-5: Minimum Load To Hot Standby

 

Definition

 

Outlines the sequence in which systems are removed from service during a plant shutdown from Mode 1 to Mode 3:

 

Complete final unloading of the turbine.

 

Reduce power level to Mode 2 and complete secondary plant shutdown.

 

Shutdown the reactor and enter Mode 3.

 

Term

Precautions and Limitations

 

 

Definition

 

Prerequisites

 

Reactor power <20%.

 

Tave at program value.

 

Tave program for 20% power is ~551°F.

 

 

 

Reactor power should be £ 8% if SG level control is on BF40 only.

 

For a planned Turbine Trip, the req’s of PT.TRB-0003 may be satisfied by direct observation of the control or governor valves during the trip, as long as there has been no evidence of malfunction of each valve during normal operation.

 

If MSIV closure is required, make sure that Gland Seal is supplied by somebody else!

 

If a manual Reactor Trip is planned and Steam Dumps are available, the Turbine should remain in service with the Dumps in Tave Control Mode for a smoother transition to EOP-TRIP-1.

 

 

 

Term
MTC >541deg F
Definition

 

Attachment 1, Maintaining Minimum Temperature for Criticality, contains instructions for action required if Tave is £541°F.

 

 

 

≤535°F à you’re done; got to TRIP

 

The only time Rods can be used is after Tavg is rising (temp control regained) and:
            RCS is now ≥541°F        or         <541°F for <15 minutes

 

 

 

Bases for Minimum Temperature for Criticality (TS 3.1.1.4)

1)  MTC is in the analyzed range  (TS 3.1.1.3, max positive=0 delta k/k/°F, BOL, max negative= -4.4 E-4 delta k/k/°F, EOL)

2)  Protective instrumentation within the operating range

3)  P-12 interlock above setpoint (Tave >543°F)

4)  PZR is capable of being operable with a steam bubble

5)  Pressure vessel above RTNDT

 

Term
AFW Pump Operation for Shut down
Definition

 

If 23 AF pump is providing flow, the AF21s are run down to minimum and the motor-driven AF pumps are started. Feed is set to at least 10E4 lbm/hr to each SG prior to the trip to “reduce the likelihood” of an auto start.

 

 

 

Term
What are the capacities of the Steam Dump valves and what is total dump capacity?
Definition

 

Answer:  Groups 1 and 2 valves - 3.33% steam flow/valve, Groups 3 and 4 valves - 5.33% steam flow/valve, total capacity ~52% steam flow.

 

Term

 

Inputs, logic and purpose of P-10.

 

Definition

 

Answer:  2/4 NIS Power Range channels >10%, allows manual blocking of Power Range High Flux Low setpoint (25%) and Intermediate Range High Flux trip setpoint (current equivalent for 25% power) .

NOTE:  In this case, while lowering load, P-10 will be ENABLING automatic RPS trips vs allowing blocking.  This is done automatically when 3/4 Power Range NI channels are <10%.

 

Term

 

Describe the inputs, logic and purpose of P-7.

 

Definition

 

Answer:  Below P-7 energized (actuated) when both P-10 and P-13 conditions no longer exist (P-13, PT-505 and PT-506 both less than pressure equivalent of 10% load
P-10, 3/4 PR NIS channels <10% power).

 

Below P-7 automatically blocks:

 

1)    PZR level high (92%) reactor trip on 2/3 channels, 

 

2)    PZR low pressure reactor trip 2/4 channels <1865 psig,

 

3)    RCP bus undervoltage/underfrequency on H or E and F or G bus reactor trip,

 

4)    Loss of flow in 2/4 loops sensed by 2/3 detectors per loop reactor trip (i.e., all RCPs could trip with no reactor trip)

2 RCP breakers open

Term

 

Inputs, logic, and purpose of P-6.

 

Definition

 

Answer:  1/2 IR channels >1E-10 amps and rising actuates P-6 (deenergizes) and allows blocking of 1/2 SR High Flux trip at 1E5 cps (allows deenergizing SR High Voltage).

2/2 IR channels <7E-11 amps and lowering automatically unblocks SR High Flux trip (energizes SR High Voltage).

 

Supporting users have an ad free experience!