Term
Battery
Describe the 24VDC batteries. |
|
Definition
-Batteries #14 & #15. -Each battery has 2 chargers. -15 powered by MCC-143A. -14 powered by MCC-133A. |
|
|
Term
Battery
Describe the loads off of 15 battery. |
|
Definition
-SRMs 21/22. -IRMS 11/12/13/14. -Containment H2/O2 analyzer. -Process rad monitors and auxiliaries. |
|
|
Term
Battery
Describe the loads off of 14 battery. |
|
Definition
-SRMs 23/24. -IRMs 15/16/17/18. -Containment H2/O2 analyzers. -Process rad monitors and auxiliaries. |
|
|
Term
Battery
Describe the 125VDC batteries. |
|
Definition
-#11 & #12 batteries. -Each has 1 battery charger. -Also each shares 1 swing charger that can only charge 1 battery at a time. -11 battery charger powered by MCC-133A. -12 battery charger powered by MCC-143A. -Swing charger powered by MCC-142A. |
|
|
Term
Battery
Describe major loads off of 11 and 12 batteries. |
|
Definition
-Control power to control boards, switchgear, and power to emergency lighting. |
|
|
Term
Battery
Describe the 13 battery. |
|
Definition
-Both 125/250VDC (depending on taps). -Has 3 chargers (1 is swing charger) all powered from MCC-134. |
|
|
Term
Battery
Describe the 16 battery. |
|
Definition
-Both 125/250VDC (depending on taps). -Has 3 chargers (1 is a swing charger) all powered from MCC-144. |
|
|
Term
Battery
Describe the major loads from 13 battery. |
|
Definition
-D311/313 control power. -Low low set. -MCC-133B control power. -RCIC stuff. -Plant evac siren. -Div I 120VAC UPS Y71. -Recirc MGs emerg LO pump. -Outboard MSL drains. -RHR s/d cooling outboard. -RHR disch to rad wast outboard. -RWCU inlet outboard. |
|
|
Term
Battery
Describe the major loads from 16 battery. |
|
Definition
-HPCI stuff. -Div II 120VAC UPS Y81. -125VDC control power to HPCI. -125VDC optical isolators. -low low set. -ASDS. -ECCS. |
|
|
Term
Battery
Describe the major loads from 17 battery. |
|
Definition
-Emergency bearing oil pump. -Emergency seal oil pump. -Backup power to process computers. |
|
|
Term
Battery
Describe the 17 battery. |
|
Definition
-250VDC. -Has 1 charger normally powered from LC-108, can also be charged by LC-107 or 13DG. -Part of Y-91. |
|
|
Term
Battery
Describe loss of 11 battery. |
|
Definition
-11/13 RHR pump min flow valves open. -11 EDG field will not flash. -11 recirc scoop tube lock. -RCIC (remote turbine trip inop). -Core spray A (auto initiation inop). |
|
|
Term
Battery
Describe loss of 12 battery. |
|
Definition
-HPCI suction valves fail open. -RCIC suction auto transfer to TORUS. -12/14 RHR pump min flow valves open. -12 EDG field will not flash. -12 recirc scoop tube lock. -HPCI (remote turbine trip inop). -Core spray B (auto initiation inop). |
|
|