Term
Sta Coo
Describe the functions of stator cooling. |
|
Definition
-Circulate low conductivity water through the stator windings. -Provide cooling water to the exciter rectifier banks. |
|
|
Term
Sta Coo
Describe the limit for stator current with no stator cooling. |
|
Definition
|
|
Term
Sta Coo
Describe the stator cooling heat exchangers. |
|
Definition
-HXs aligned in series. -Shell side has stator cooling. -Service water through tubes. |
|
|
Term
Sta Coo
Describe system temp control. |
|
Definition
-Temperature control valve that regulates by bypassing the heat exchanger. -Maintains 40-46C. -Normally set at 43C. |
|
|
Term
Sta Coo
Describe the rectifier filter d/p. |
|
Definition
-Filters must be replaced at next shutdown if dP reaches 8psid. -Or every 24 months. |
|
|
Term
Sta Coo
Describe the max flow and replacement criteria for the deionizer. |
|
Definition
-Max of 50gpm (norm 45) to prevent channeling. -Replace after 24 months ops. -Or 1st scheduled S/D if dP reaches 15psid. -Or conductivity > 0.5umho. |
|
|
Term
Sta Coo
Describe the dual strainer max dP. |
|
Definition
-Swap the strainer at 8psid. |
|
|
Term
Sta Coo
Describe the storage tank levels and alarms. |
|
Definition
-Normal level is 1/2 ful. -High or low level if 4" from normal in either direction. |
|
|
Term
Sta Coo
Describe the temperature runback/alarm. |
|
Definition
-Turbine runback at 86C. -Alarm at 81C. |
|
|
Term
Sta Coo
Describe when turbine runback circuitry is enabled. |
|
Definition
If stator amps are > 4000amps. |
|
|
Term
Sta Coo
Describe the runback signals. |
|
Definition
-Low generator inlet pressure: 38.6psig (236gpm). -High generator outlet temperature: 86C. |
|
|
Term
Sta Coo
Describe the runback time delays and stops. |
|
Definition
-Lowers speed at 2%/min. -Gen current not less than 12,000 amps in 2 min then turbine trip. -Gen current not less than 4,000 amps in 3.5 min then turbine trip. -Stops if initiation signal clears. -Stops if stator current < 4000 amps. |
|
|
Term
Sta Coo
Describe stator cooling pressure control. |
|
Definition
-Control valve that keeps stator cooling pressure at least 3# less than generator H2 pressure. -Has stops at 385 and 315 gpm. |
|
|
Term
Sta Coo
Describe the stator cooling pump standby features and power supply. |
|
Definition
-10# less than normal standby starts. -20# less than normal reserve pump starts. -MCC-121/131. |
|
|
Term
Sta Coo
Describe the rectifier path flow alarms. |
|
Definition
-Normal flow is 20gpm. -Low flow at 17gpm. |
|
|