Stator Cooling (Sta Coo)
BWR Systems
15
Other
Not Applicable
07/16/2012

Additional Other Flashcards

 


 

Cards

Term
Sta Coo

Describe the functions of stator cooling.
Definition
-Circulate low conductivity water through the stator windings.
-Provide cooling water to the exciter rectifier banks.
Term
Sta Coo

Describe the limit for stator current with no stator cooling.
Definition
4899amps.
Term
Sta Coo

Describe the stator cooling heat exchangers.
Definition
-HXs aligned in series.
-Shell side has stator cooling.
-Service water through tubes.
Term
Sta Coo

Describe system temp control.
Definition
-Temperature control valve that regulates by bypassing the heat exchanger.
-Maintains 40-46C.
-Normally set at 43C.
Term
Sta Coo

Describe the rectifier filter d/p.
Definition
-Filters must be replaced at next shutdown if dP reaches 8psid.
-Or every 24 months.
Term
Sta Coo

Describe the max flow and replacement criteria for the deionizer.
Definition
-Max of 50gpm (norm 45) to prevent channeling.
-Replace after 24 months ops.
-Or 1st scheduled S/D if dP reaches 15psid.
-Or conductivity > 0.5umho.
Term
Sta Coo

Describe the dual strainer max dP.
Definition
-Swap the strainer at 8psid.
Term
Sta Coo

Describe the storage tank levels and alarms.
Definition
-Normal level is 1/2 ful.
-High or low level if 4" from normal in either direction.
Term
Sta Coo

Describe the temperature runback/alarm.
Definition
-Turbine runback at 86C.
-Alarm at 81C.
Term
Sta Coo

Describe when turbine runback circuitry is enabled.
Definition
If stator amps are > 4000amps.
Term
Sta Coo

Describe the runback signals.
Definition
-Low generator inlet pressure: 38.6psig (236gpm).
-High generator outlet temperature: 86C.
Term
Sta Coo

Describe the runback time delays and stops.
Definition
-Lowers speed at 2%/min.
-Gen current not less than 12,000 amps in 2 min then turbine trip.
-Gen current not less than 4,000 amps in 3.5 min then turbine trip.
-Stops if initiation signal clears.
-Stops if stator current < 4000 amps.
Term
Sta Coo

Describe stator cooling pressure control.
Definition
-Control valve that keeps stator cooling pressure at least 3# less than generator H2 pressure.
-Has stops at 385 and 315 gpm.
Term
Sta Coo

Describe the stator cooling pump standby features and power supply.
Definition
-10# less than normal standby starts.
-20# less than normal reserve pump starts.
-MCC-121/131.
Term
Sta Coo

Describe the rectifier path flow alarms.
Definition
-Normal flow is 20gpm.
-Low flow at 17gpm.