Term
|
Definition
Impractical and time consuming to test all joints,pipes and connections. .a localised test to prove the integrity of an installation .Performed from a single point on the installation,normally at primary meter. .Uses pressure decay as an indicator to the integrity of an installation. Pressurise a gas system and isolate the pressure source. provided there is no leakage of gas. the pressure will remain constant over a calculated period of time. If gas leak is present,the pressure within the system would start to decay. Pressure decay is recognised by a pressure drop on the gauge relative to the severity of the leak. |
|
|
Term
|
Definition
.Pressure Gauge-either water or electronic. .Testing Tee (where required if testing with air). Aspirator to pressurise the system where air is used as the test medium. |
|
|
Term
|
Definition
|
|
Term
|
Definition
Any gas installation with LPG/Air,Natural Gas or LPG where the MOP does not exceed 2bar Pipework upto 35mm U16/G10 Meters Max badged capacity does not exceed 16m3/h |
|
|
Term
|
Definition
Uses pressure decay as an indicator to the integrity of an installation. |
|
|
Term
|
Definition
|
|
Term
|
Definition
Must be capable of reading to at least 0.5mbar |
|
|
Term
|
Definition
Must be capable of being read to at least 0.1mbar |
|
|
Term
No Perceptible Movement for a water gauge |
|
Definition
|
|
Term
No perceptible movement for an electronic gauge |
|
Definition
|
|
Term
|
Definition
Carried out between 7 and 10mb |
|
|
Term
|
Definition
Carried out between 18 and 19mb |
|
|
Term
|
Definition
|
|
Term
|
Definition
Carried out between 7mb and 10mb |
|
|
Term
|
Definition
Carried out between 20 and 21mb |
|
|
Term
Tightness Test New Installations(with or without appliances connected) will pass if? |
|
Definition
No Perceptible Movement and no smell of gas |
|
|
Term
Tightness Test Existing with NO appliances connected(i.e pipework only) will pass if? |
|
Definition
No Perceptible Movement and no smell of gas |
|
|
Term
Tightness Test Existing WITH appliances connected will pass if? |
|
Definition
Pressure drop does NOT exceed values in table And No smell of Gas. |
|
|
Term
Tightness Test <28mm Pipe E6 Meter<6m3/h or no meter |
|
Definition
|
|
Term
Tightness Test <28mm pipe U6/G4 meter < 6m3/h pressure drop is..? |
|
Definition
|
|
Term
Tightness Test <28mm U16/G10 >6m3/h <16m3/h pressure drop is ? |
|
Definition
|
|
Term
Tightness Test >28mm <35mm E6 Meter<6m3/h or no meter PRESSURE DROP IS..? |
|
Definition
|
|
Term
Tightness Test >28mm <35mm pipe bore U6/G4 meter < 6m3/h PRESSURE DROP IS..? |
|
Definition
|
|
Term
Tightness Test >28mm <35MM U16/G10 >6m3/h <16m3/h pressure drop is ? |
|
Definition
|
|
Term
Diaphragm U6/G4 Purge volume for 28mm |
|
Definition
|
|
Term
Ultrasonic E6 meter Purge volume for 28mm |
|
Definition
|
|
Term
Diaphragm U16/G10 Purge volume <28mm >28mm |
|
Definition
|
|
Term
Diaphragm U6/G4 Purge volume for >28mm |
|
Definition
|
|
Term
Ultrasonic E6 Purge volume for >28mm |
|
Definition
|
|