Term
Open Flued Appliance COMPARTMENT Venting to OUTSIDE |
|
Definition
High Level 5cm2/kW Low Level 10cm2/kW
In Room-NIL [image] |
|
|
Term
Open Flued Appliance COMPARTMENT Venting to ROOM |
|
Definition
High Level 10cm2/kW Low Level 20cm2/kW Room Vent-Max Heat Input(net)-7kW x 5cm2[image] |
|
|
Term
|
Definition
Max Heat Input(Net)-7kW x 5cm2 |
|
|
Term
Room Sealed Appliance COMPARTMENT Venting to OUTSIDE |
|
Definition
High Level-5cm2/kW Low Level -5cm2/kW In Room-NIL[image] |
|
|
Term
Room Sealed Appliance COMPARTMENT Venting to ROOM |
|
Definition
High Level 10cm2/kW Low Level 10cm2/kW In Room-NIL[image] |
|
|
Term
Room Sealed Appliance Room |
|
Definition
|
|
Term
Ventilation NET Heat Input Value |
|
Definition
Divide the gross value by 1.1 |
|
|
Term
|
Definition
Air that can leak into buildings through windows,doors,floorboards walls etc |
|
|
Term
|
Definition
No allowance can be made for adventitious ventilation |
|
|
Term
|
Definition
Specially designed to prevent spread of fire. Normally an insert with metal framework,open latticework of heat sensitive material |
|
|
Term
Design width of Vent grill |
|
Definition
Permits entry of a ball of 5mm diameter but prevents entry of a ball of 10mm diameter |
|
|
Term
Installation of a vent in internal wall or door |
|
Definition
No greater than 450mm from floor level |
|
|
Term
Fluess appliance ventilation requirements |
|
Definition
Consult M.Is or table in BS5440-2 Any air vent required must be direct to outside |
|
|
Term
Ventilation for flueless space heater in a ROOM |
|
Definition
1.Convert kW to Watts by x the net heat input by 1000 2.Then DIVIDE by the volume of the room Answer must be 45W/m3 or less |
|
|
Term
Gas Fired Appliances Minimum Flue Diameter is |
|
Definition
|
|